• 8-8km Tdrl 950 Cable Fault Location for Automatic Measurement
  • 8-8km Tdrl 950 Cable Fault Location for Automatic Measurement
  • 8-8km Tdrl 950 Cable Fault Location for Automatic Measurement
  • 8-8km Tdrl 950 Cable Fault Location for Automatic Measurement
  • 8-8km Tdrl 950 Cable Fault Location for Automatic Measurement
  • 8-8km Tdrl 950 Cable Fault Location for Automatic Measurement

8-8km Tdrl 950 Cable Fault Location for Automatic Measurement

Model Number: Tdrl 950
Measurement Distance: 0-8km
Impulse Range: 30V
Customization:
Shipping Cost:

Estimated freight per unit.

about shipping cost and estimated delivery time.
Payment Method: visa mastercard discover JCB diners club american express T/T
  Initial Payment Full Payment
Currency: US$
Return&refunds: You can apply for a refund up to 30 days after receipt of the products.
From payment to delivery, we protect your trading.
8-8km Tdrl 950 Cable Fault Location for Automatic Measurement pictures & photos
8-8km Tdrl 950 Cable Fault Location for Automatic Measurement
US $399-4,999 / Piece
Min. Order: 1 Piece
Diamond Member Since 2011

Suppliers with verified business licenses

Secured Trading Service
Tianjin, China
High Repeat Buyers Choice
More than 50% of buyers repeatedly choose the supplier
Years of Export Experience
The export experience of the supplier is more than 10 years
In-stock Capacity
The supplier has In-stock capacity
100% Finished Products Inspection
The supplier inspects 100% of finished products.
to see all verified strength labels (22)

Basic Info.

Model NO.
TDRL 950
Impulse Width
80ns-5μs, Auto Adjustments
Adjustable Gain Range
0-80dB
Blind Zone
1m
Wave Velocity Range
100-300m/μs
Weight
0.42kgs Without Battery
Supply Power
AA Battery X 6PCS
Elevation
<4500m
Transport Package
Standard Export Packing
Specification
225mmx105mmx50mm
Trademark
Grewin
Origin
China
HS Code
9028901000
Production Capacity
50000PCS/Year

Product Description

TDRL 950 Cable Fault Location

The TDRL-950 Cable Fault Locator is a portable handhold device used for locating the broken fault, cross fault, insulation fault and so on. It can be used to measure the cable length, wave velocity and distinguish the middle joints and terminals.
It is a simple locating device, adopts to kinds cable and specially, the telecomputer cable.


TDRL 950 Cable Fault Location Function Introduction:
  1. TDRL(Time Domain Reflectometry)method make it possible to measure broken fault, cross fault, insulation fault and so on.
  2. Automatic measurement
  3. Auto power-off when sleeping and low battery voltage
  4. Friendly user interface, easy to operate
  5. Supply by dry batter or recharge battery
  6. Handheld device, easy to carry
     

TDRL 950 Cable Fault Location Tech. Specifications

Measurement distance 0-8km
Resolution ratio 0-1km,below 1m;
2km,below 2m;
4-8km,below 8m
Impulse range 30V
Impulse width 80ns-5μs,auto adjustments
Blind zone 1m
Wave velocity range 100-300m/μs
Adjustable gain range 0-80db
Supply power AA battery x 6pcs
Volume 225mm×155mm×50mm
Weight 0.42kgs without battery
Operating Temperature  -10ºC-40ºC
Humidity 5-90%RH
Elevation <4500m
Device configurations 
TDRL-950 cable fault locator including main engine, testing lines and documents. Main engine as below
8-8km Tdrl 950 Cable Fault Location for Automatic Measurement

 
Basic function:
1/2  
  • Change testing range
Cursor       
  •         Move the cursor
3/4  
  • Adjust single gain
On/Off
  • Power on/off
 
  • Open/close screen backlight
Locate 
  • Locating the fault point automatically
Test  
  • Click for testing once while pressing for more than 3 seconds to begin continuous testing and waveform displaying
Other function:Press shift(  ) and other button together
Shift&V+/V-
  • Change the wave velocity
Shift&   / 
  • Zoom in or out the waveform 
Shift&Save
  • Storage the waveform
Shift&Comp
  • Display the saved waveform and current waveform together for comparing
Shift%Auto
  • Find the suitable testing range and the most possible fault point
Display interface when working
8-8km Tdrl 950 Cable Fault Location for Automatic Measurement

Specification
1
  • Transmitted impulse
2
  • Battery lever
3
  • Temporarily store mark
4
  • Comparing mark
5
  • Cursor
6
  • Distance
7
  • Reflection impulse of cable fault point
8
  • Wave velocity
9
  • Measuring range
10
  • Gain
11
  • Display scale
Fault determined:
When cable fault appeared, pls first judge fault feather and broken lever. The TDR fault are divided into three kinds as below:
  1. Disconnection fault: cable broken and communication
disconnect.
  1. Crossing fault which is generally classified into three kinds:
grounding fault, self-crossing fault, and common crossing. During these conditions, the insulating layer was broken even touched to affect the communication quality.  

Defective insulation fault:
The cable corn is entranced by moisture or water to reduce the insolation resistance.The difference between this and above crossing fault is this has a big resistance, common over thousand Ohms.  

In generally, for above first and second fault, it's easy to detect by pulse test, but for the third, user should consider the cable path, time of fault, range of the fault, environment and so on.

Lines connection
Before testing,pls disconnection inside devices with problem cable first.
Then inside testing to make sure the rough location of the fault point.
After then,go to the filed to pinpoint the fault.
When testing,connect the lines plug with testing interface, and clamp the fault cable.

 
Choose testing range
  1. To get complete testing waveform,the testing range should
be several hundred meters longer than the length of the cable.For example,if the cable is 900m,the testing range should be 2km.when found the fault point closer,reduce the range accordingly.
  1. This device offer below six testing ranges to choose, 125m,  
250m,500m,1km,2km and 4km.
  1. Press 1 or 2 button to change the testing range.Check
'basic function' for reference. 
  1. Pls notice that,the device test once automatically after
once range changing.
  1. Setting the wave velocity
According different cable material,user should choose different wave velocity.
Shift&V+/-
  • Change the wave velocity
Adjustable range
  • 100-300m/μs 

*Some common cable pls take below for reference:
Plastic power cable
  • 201m/μs 
Polyethylene power cable
  • 192m/μs 
Oil filled cable
  • 160m/μs 
paper pulp insulated cable
  • 216m/μs 
Accurate measurement,use the method in page ,to calibrate the wave speed
 
Gain adjustment
3/4 button  
  • Adjust single gain,increase or reduce
  • Auto testing for every time the gain changing
 
  1. Gain adjustment
Gain is the magnification times of the signal. This could change the wave amplitude. Common in every range, there re default gain, but if it' s not suitable, you also could choose manual adjustable.
Gain adjustment: press Gain +/-to change the signal gain. Every time change the gain, the device will test automatically.
  1. Cursor positioning
The beginning of the reflection impulse waveform is the fault 
position. When move the cursor into this position, for example, the virtual cursor in pic.5,there will be a distance appear in the right corner of the screen which is the fault distance.
Pls notice, if the cursor on other position, the distance is not useful. 
*Auto position: Press "Auto" key, device will automatically position. If deviation, please position manual. 
*Maunal position: Press    &    to move the curve left and right.

8-8km Tdrl 950 Cable Fault Location for Automatic Measurement
*This waveform is a typical example of crossing fault.The dot cursor position is the fault position,453m.
If the waveform is downward, the fault is broken fault.

Waveform zoom in and zoom out
To get a higher resolution, please use zoom in/out function.
Press    button to zoom in and   to zoom out.
*When 'Zoom out', auto positioning function is not workable.

 

Waveform temporary storage and compare
It's easier to distinguish the fault type through comparing the good cable and fault cable.
First, testto get the fault waveform and press TS to keep it. There's a TS mark on the left corner of the screen.
Then test a good cable under the same condition. 
Press Comp. to show the two waveforms together and there'll be a compare mark on the screen.
Find the fault point from check the difference of the two waves. 

Auto testing
Press Auto key, the device will automatically test, choose range and position cursor. The result is only for reference.

 
Continuous testing
Longtime press Test up to 3 sec. and the device will come in the continuous testing mode. And will stop after 1 minute. Or you could press Test button again to stop.
This function is common used to routing inspect multi-pair core wire.


 
Wave velocity correct
According now the cable length, we could correct the wave velocity.
Use same known length cable and test the opposite terminal open circuit and short circuit waveform and compare. Move the virtual cursor to the obvious difference and change the wave velocity to make the tested distance same as the known length. Then the velocity is the real one of this cable.


Instrument Maintenance
Charge
Standard configuration is 6AA NI-MH battery ,capacity above 
1300mAH is better. Dry battery is also ok if no NI-MH battery if necessary but need high capacity ones.
*Please notice don't put the battery backwards.



TDRL 950 Cable Fault Location Product:

8-8km Tdrl 950 Cable Fault Location for Automatic Measurement
8-8km Tdrl 950 Cable Fault Location for Automatic Measurement



Certificate:

8-8km Tdrl 950 Cable Fault Location for Automatic Measurement


Company Introduce:
Tianjin Grewin Technology Co.,Ltd have twenty years producing experience, located in Tianjin , China, our company have professional design term, advanced technology and equipment, especially pay great attention to its business philosophy "Quality and Honesty First". Grewin is specialized in the design and manufacture of  intelligent power meter and testing device, such as Three/single Phase Multi function Meter, Power Monitoring device,Intelligent Pipe Locator,Route tracing/Cable identification/depth measurement/grounding fault location and so on;especially the EPM and TPM product got inland and over sea's clients praise, and established OEM or ODM relationship. Our products have passed and obtained ISO9001 certificate ,CE certificate,SGS approval, and IEC report. We have developed good cooperative relationship with valued customers around the word, have first class product quality and one basket value-added after sales service along with the fast efficient solution. Grewin has won its brand in word wide.
Contact Information:

Alice Lee
TIANJIN GREWIN TECHNOLOGY CO.,LTD
Add:Meinian Plaza.No .16 Dongting Road,Hexi Distr,Tianjin,China .
 
 
Web: transformer.en.made-in-china.com 
 
Mobile:+86-13072088960 


 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now